NA2XSY 1X150 mm2

Description

Description

Standards

  • Product
    IEC 60502-2

Application:

These are cables with low dielectric losses used in energy network with sudden load changes. Laid in residental or industrial areas, underground or in ducts.

 

Construction:

  1. Conductor:Aluminium
  2. Conductor screen:Semi-conducting compound (XLPE)
  3. Insulation:XLPE
  4. Insulation screen:Semi-conducting compound (XLPE)
  5. Semi-conducting tape:Crape tape
  6. Metallic screen:Concentric / Copper wires + copper tape
  7. Outer sheath:PVC

 

Marking:

 NEXANS  IEC 60502 NA2XSY 1x150/16 8,7/15 kV YEAR

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Aluminum
Conductor shape
Circular stranded (RM)
Material of the inner semi-conductor
XLPE
Insulation
XLPE (Cross-linked Polyethylene)
Material of the external semi-conductor
XLPE
Screen
Copper wire + copper tape
Outer sheath
PVC
Conductor flexibility
Stranded class 2
Sheath colour
Red

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
150 mm²
Nominal outer diameter
38.0 mm
Approximate weight
1920 kg/km
Delivery reel size for 1000m
- cm
Screen section
50 mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
8,7/15 kV
Max. DC resistance of the conductor at 20°C
0.206 Ohm/km
Approx. inductance, flat formation
- mH/km
Approx. inductance, trefoil formation
- mH/km
Nominal phase capacitance
- µF / km
Perm. current rating buried 20°C - flat formation
- A
Perm. current rating buried 20°C - trefoil formation
281 A
Perm. current rating in air 30°C - flat formation
440 A
Perm. current rating in air 30°C - trefoil formation
- A
Permissible short circuit current conductor 1s
14.1 kA
Permissible short circuit current screen 1s
- kA

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 90 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-1-2
Bending factor when laying
12 (xD)
Max. conductor temperature in service
90 °C

Resources

Resources

Declaration of Performance

  • Declaration of Performance n° : 1001075-TRDE
  • Certification Date : 4/11/22
  • AVCP (Assessment and Verification of Constancy of Performance) : System 3
  • Notified body : 1783
  • Declared performance : Eca

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close