AL/XLPE/WBT/CWS/WBT/FL/LSZH 1X185/35 mm2

Description

Description

Standards

  • Product
    EN 50575; IEC 60228; IEC 60502
  • Test
    IEC 60332-3-24; IEC 60754-1; IEC 60754-2

Application

These are cables with low dielectric losses used in energy networks with sudden load changes where mechanical stresses expected. Laid in residential or industrial areas, underground or in ducts.

Construction

  1. Conductor:Aluminium
  2. Conductor screen:Extruded semi-conductor
  3. Insulation:XLPE
  4. Insulation screen:Extruded semi-conductor (Strippable)
  5. Semi-conducting tape:Water swelling tape
  6. Metallic screen:Copper wires+counter helix tape
  7. Taping: Water swelling tape on the metallic screen
  8. Radial water blocking: Longitudinal aluminium foil sticking to Protective Sheath
  9. Outer sheath:LSZH

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Plain aluminium
Conductor shape
Round, stranded
Material of the inner semi-conductor
XLPE
Insulation
XLPE (chemical)
Material of the external semi-conductor
XLPE
Screen
Copper wires with counter helix of copper tape
Outer sheath
LSZH
Halogen free
IEC 60754-1

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
185 mm²
Approximate weight
1710 kg/km
Maximum outer diameter
38.3 mm
Minimum outer diameter
34.5 mm
Minimum outer sheath thickness
1.48 mm
Nominal insulation thickness
5.5 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
12 / 20 (24) kV
Max. DC resistance of the conductor at 20°C
0.164 Ohm/km
Impedance at 50 Hz
0.23 Ohm
Perm. current rating buried 20°C - trefoil formation
317 A
Perm. current rating in air 30°C - flat formation
504 A
Reactance at 50 Hz
0.11 Ohm/km
Short Circuit Current 0,3 s Max
- kA
Short Circuit Current 1 s Max
17.4 kA
Voltage Drop
0.4 V/A.km

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Flame retardant
IEC 60332-3 Cat. C
Bending factor when laying
12 (xD)
Gases corrosivity
IEC 60754-1; IEC 60754-2
Longitudinal water tightness
Yes
Radial water tightness
Yes
Smoke density
IEC 61034-2
U.V resistance
Yes

Resources

Resources

Declaration of Performance

  • Declaration of Performance n� : 1001319-TRDE
  • Certification Date : 4/16/25
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : 1008
  • Declared performance : Cca-s1,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close