AL/XLPE/CWS/LSZH 3x240/25 mm2
AL/XLPE/CWS/LSZH 3x240/25 mm2
12/20 kV XLPE insulated, LSZH sheathed cables with aluminium conductor
Read more- Nexans ref. : 10590624
- Country ref. : TR
- EAN : 8680969251914
Description
Description
Standards
-
ProductBS 7835
Application
Suitable for installations in energy networks where for safety reasons low smoke halogen free and flam retardant cables are specified. The cable is suitable for installation undergorund, in ducts or in air.
Construction
- Conductor:Aluminium
- Conductor screen:Extruded semi-conductor
- Insulation:XLPE
- Insulation screen:Extruded semi-conductor (Fixed Bonded) copper wires with counter helix of copper tape
- Outer sheath:LSZH
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Conductor shape
Material of the inner semi-conductor
Insulation
XLPE
Material of the external semi-conductor
Screen
Copper wires + copper tape
Armour type
Outer sheath
LSZH
Sheath colour
Black
Dimensional characteristics
Dimensional characteristics
Number of cores
3
Conductor cross-section
240 mm²
Nominal outer diameter
75.1 mm
Approximate weight
6970 kg/km
Delivery reel size for 1000m
- cm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
12/20 kV
Max. DC resistance of the conductor at 20°C
0.125 Ohm/km
Nominal inductance
- mH/km
Nominal phase capacitance
- µF / km
Perm. current rating buried 20°C - flat formation
338 A
Perm. current rating in air 30°C - flat formation
415 A
Permissible short circuit current conductor 1s
22.6 kA
Permissible short circuit current screen 1s
- kA
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Flame retardant
IEC 60332-3 Cat. C
Bending factor when laying
10 (xD)
Gases corrosivity
IEC 60754-2
Max. conductor temperature in service
90 °C
Smoke density
IEC 61034-2
Resources
Resources
Declaration of Performance
- Declaration of Performance n� : 1001333-TRDE
- Certification Date : 7/10/25
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 1008
- Declared performance : Dca-s1,d2,a1