NX300 1x50 mm2 BS 6387
NX300 1x50 mm2 BS 6387
0,6/1 kV single core low smoke halogen free, flame and fire resistant cables
Read more- Nexans ref. : 10532111
- Country ref. : TR
- EAN : 8680969069090
Description
Description
Standards
-
ProductBS 7846
-
TestBS 6387
Application:
Rafineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plants , data processing centers, business centers where there is a concentration of sensitive to fire
Construction:
- Conductor: Copper
- Fire barrier: Mica tape
- Insulation: XLPE
- Outer sheath: LSZH
Marking:
NEXANS i NX300 Number of cores x cross section 600/1000 V IEC 60331-21 BS 6387 Cat.C LPCB 946c/01 "YEAR"
*BS 6387 CAT CWZ for single core 1 to 35 sqmm
*BS 6387 CAT C for single core 50 to 300 sqmm
*EN 50200 PH 120 for single core 1.5 to 35 sqmm
*IEC 60331-21 for all cross sections.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Copper
Outer sheath
HFFR (Halogen Free Flame Retardant)
Insulation
XLPE + Mica tape
Sheath colour
Black
Conductor flexibility
-
Conductor shape
Circular stranded (RM)
Core identification
Brown
Halogen free
IEC 60754-1
Dimensional characteristics
Dimensional characteristics
Number of cores
1
Approximate weight
550 kg/km
Average insulation thickness
- mm
Conductor cross-section
50 mm²
Conductor diameter
- mm
Nominal outer diameter
- mm
Nominal outer sheath thickness
- mm
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
0,6/1 kV
Max. DC resistance of the conductor at 20°C
0.387 Ohm/km
Permissible current rating in open air
207 A
Permissible current rating when buried
153 A
Usage characteristics
Usage characteristics
Fire resistant
BS 6387 CWZ
Smoke density
IEC 61034
Gases corrosivity
IEC 60754-2
Flame retardant
-
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 60 °C
Short-circuit max. conductor temperature
250 °C